Nail salon ventilation requirements: the 50 cfm rule explained

Under the model mechanical code used across most of the United States, general room ventilation is not enough for a nail salon. Each station needs its own exhaust. Here is what the rule says and how it changes your build-out.

The rule

What the International Mechanical Code requires

Source capture at every station

The International Mechanical Code (IMC) requires a source capture system at each manicure and pedicure station. Each system must exhaust at least 50 cubic feet per minute, and the captured air goes to the outdoors.

Inlets within 12 inches

Where a table or pedicure station does not come with factory-installed exhaust inlets, the inlets must be located no more than 12 inches horizontally and vertically from the point of chemical application.

Room ventilation still applies

The same code table sets outdoor-air and exhaust rates for the salon as a whole. Where the station systems run continuously while the salon is occupied, their airflow may be counted toward the room exhaust rate. Your mechanical engineer does this calculation.

Local adoption varies

States and cities adopt different editions of the IMC and amend them. Utah, for example, wrote its own version that allows a filtered recirculating unit as an alternative. Ask your building department which edition and amendments it enforces before you design.

Source

ICC CodeNotes on nail salon exhaust

The International Code Council, which publishes the IMC, has a short explainer on these requirements based on the 2021 edition.

Read the ICC explainer →

From our model

Exhaust and ductwork drawn before construction

Model with furniture hidden, showing plumbing, electrical and HVAC
Model with furniture hidden, showing plumbing, electrical and HVAC
Nail bar served by dedicated exhaust fans in the sample model
Nail bar served by dedicated exhaust fans in the sample model

Views from BAT's own 3D model of a 2,495 sf nail salon.

Design

What the rule changes in your build-out

A duct route to the outside

Every station needs a path to a fan and from the fan to the roof or an outside wall. Confirm with the landlord that a roof or wall penetration is allowed before you sign the lease.

Make-up air

Air that is exhausted has to be replaced. In a salon with many stations the make-up air affects the size of the heating and cooling system.

Tables with built-in inlets or field-installed arms

Manicure tables with factory-installed inlets keep the room tidy. Field-installed inlets work too, provided they sit within the 12-inch limit.

Noise and controls

Place fans away from the service floor where possible, and wire the system to run whenever the salon is occupied.

Before you sign the lease

  • Ask whether roof or wall penetrations are allowed
  • Check the capacity of the existing HVAC unit
  • Count stations, then multiply by 50 cfm for a first exhaust figure
  • Ask the building department which mechanical code edition applies

In the 2,495 sf sample salon BAT modeled, the drawings call for four dedicated chair and nail bar exhaust fans and two dedicated outdoor-air units. Modeling them in 3D shows early where ducts cross plumbing and lighting.

FAQ

Common questions

Is an air purifier enough for a nail salon?

Under the model IMC the source capture system exhausts to the outdoors. Some jurisdictions have amended this to allow filtered recirculating units. Check the code your city enforces.

Do pedicure chairs need exhaust too?

The IMC footnote covers both manicure and pedicure stations.

Who designs the ventilation system?

A mechanical engineer or a licensed mechanical contractor, depending on your state and the size of the project. BAT models the system in 3D so it can be coordinated with the plumbing and electrical work.